Bypass Facility :-Manual (Through Rotary Switch) / Static Bypass Switch (10 - 18 msec C/O time)*
Audible Noise :- Less Than 60 dB at 1 meter
Design ambient :- 0-50o C
Relative Humidity :- Max. 95 % Non Condensing
Enclosure :- M.S. Powder coated with castor wheels (Turbo Model without Castor wheels)
Dimensions in mm (LxWxH) :- 770x420x750- 980x500x850 - 980x500x850- 1200x570x1000
Communication:- GSM Modem for SMS Alerts to user and service center for any Fault condition, eARD
Input Auto Phase Corrector :- Builtin Input Auto Phase Correction provided in case of i/p supply Phase Reversal
Healthy Phase Selector :-For 1 ph Input UPS Healthy Phase Selector in case of Mains Supply Single Phasing
Wider Input Range :- Input supply range can be extended as per site requirement, helpful in case of Rural or sites with heavy fluctuation of mains supply
|
TECHNICAL SPECIFICATIONS LIFT UPS 6 - 40 KVA (3 ph- 3 ph) |
|||||||||
|---|---|---|---|---|---|---|---|---|---|
| Model | ELOS-06 | ELOS-08 | ELOS-12 | ELOS-15 | ELOS-20 | ELOS-25 | ELOS-30 | ELOS-40 | |
| KVA | 6 | 8 | 12 | 15 | 20 | 25 | 30 | 40 | |
| DC BUS | 4.8 KW | 6.4 KW | 9.6 KW | 12 KW | 16 KW | 20 KW | 24 KW | 32 KW | |
| 100 % Unbalanced Laod* (optional) | |||||||||
AC INPUT
| Input voltage | 415 VAC +15, - 20 % / 230VAC +15, -20% * | ||||||||
| Input Frequency | 50 Hz +/- 6 % | ||||||||
DC CHARGER
| Battery Voltage | 72V-96V | 96V-180V | 144V - 240V | 240V-360V | 360V | ||||
| Rectifier | ATM Tech. Boost and Float mode | ||||||||
AC OUTPUT
| Technology | Mosfet / IGBT Based PWM Inverter using Micro Controller |
| Output voltage | 400 VAC +/- 2 % |
| Output Frequency | 50 Hz +/- 0.5 % |
| Output Power factor | 0.8 to 1 lag |
| Output waveform | PWM Sine wave |
| Phase Displacement | 120⁰ + 1⁰ |
| Crest Factor | 4:1 |
|---|---|
| Galvanic Isolation | Inbuilt Galvanic Isolation Transformer Provided |
| Harmonic Distortion | Less than 3 % on Linear Load |
| Transient Recovery | + 4 % from 0 to Full load and corrected within 60 msec. |
| Inverter Efficiency | 87 % - 93 % Depending on DC voltages |
INDICATIONS & ALARMS
| Indications |
Mimic Display*, Mains on, Inverter On, Battery Low, Over
Load, Output Under Voltage, Output Over Voltage, DC Over Voltage, I/p Single Phasing / Phase Reversal |
| Audible Alarm |
Intermittent beep for 30 sec. On mains fail. Battery low
pre-alarm at 80 % of Battery discharge. Intermittent Beep for all other Trip Conditions |
eARD - EMERGENCY AUTO RESCUE DEVICE*
| eARD |
Micro controller based Wireless Digital Scrolling with
Voice messeging - To Display the status - Lift is running on Mains, Lift on Battery, Battery % charge remaining, Battery Low Pre-alarm, Battery Low - DO NOT USE LIFT, Mains Supply Single Phasing- Call Electricity Board PH. No.---, Mains Supply Phase Reversal - Call Electrician PH. No.----, Project Developed By ----, RENUTRON Service Helpline No. 9371776979 |
METERING
| Digital Metering and Fault Indications |
Micro controller based Digital Scrolling LCD to Display* -
I/P voltage , O/P Voltage, Load Current, Load %, Charging
Current, Battery Voltage, % Battery Charge. Fault indications – Mains Off, O/p under voltage / over voltage, Battery Low pre alarm & Trip, DC Over voltage, Output Overload, I/p under voltage / over voltage, I/p Single Phasing / Phase Reversal |
PROTECTIONS
| Protections | Output Overload (110% -Continuous, 150% - 30 Sec, 300% - 5 seconds), Output short circuit, Battery low trip, DC over voltage, Output under voltage / over voltage, Input under voltage / over voltage, I/p Single Phasing / Phase Reversal, Over Temperature, Input Surge Protection through MOV, Common ELCB at UPS output for multiple Lifts* |